1250 kVA Emergency power system, soundproofed as an emergency power system 1250 kVA with MTU engine 18 V 2000 G 26 F
Stock No.: 1388
Completion:
Category:
Notstromaggregat Stationär
Generating Set:
stationary
Gen Set:
silent Set
Technical Data Engine:
Engine Manufacturer:
MTU
Engine Type:
18 V 2000 G 26 F
Engine No.:
in Produktion
Engine Power:
1.102 KW
Cooling:
water-cooled
Starting:
electrical 12 V DC
Rotation:
1500 rpm
Fuel:
heating oil EN 590
Fuel Consumption:
264 Liter at 100 % Load
Emission Standard:
44. BimschV |TA Luft
Engine Size:
40,2L.
Amount of Oil:
110 L.
Consumption of Combustion Air:
m³/h
Cooling Air Volume:
m³/h
Exhaust Temperature:
485 °C
Exhaust Gas Quantity m3:
12.384 m3
Exhaust Gas Quantity kg:
kg
Technical Data Generator:
Generator Manufacturer:
Stamford AvK
Gen Set:
HC Serie
Gen No.:
in Produktion
Gen Power:
1.250 kVA
Gen Amperage:
Ampere
Short Circuit Current:
Ampere
Overload:
Ampere
Voltage:
400 / 231 Volt
Voltage Controller:
elektronisch AVR
Power Factor:
cos. - phi 0,8
Rotation:
1500 rpm
Control Unit:
Setup:
automatic start
Functions:
parallel operation
Switch:
gen switch 4 pole
Delivery:
set up
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Fuel Tank:
Setup:
baseframe fuel tank with bassin
Width ca. mm:
Height ca. mm:
Depth ca. mm:
Capacity / Litre:
1000
Dimensions of unit:
Width ca. mm:
2.250
Height ca. mm:
3.958
Length ca. mm:
7.200
Weigth ca. KG:
13.500
Usage:
Stock No:
1388
State:
NEW
year of manufacture:
New
time of delivery:
on Request
Operating Hours:
neu
Location:
Verl - Germany
Price plus VAT in €:
on request:
Reserved:
nein / no
delivery contents:
New unit soon to begin production, still freely configurable.
Diesel backup power unit with an MTU diesel engine in an exhaust-optimized design, installed in a sound and weather protection hood (powder-coated in RAL 9010) with lockable maintenance doors on the side.
The 990 liter tank is integrated into the base frame including the oil collecting pan.
Fully automatic control make ComAp type: IG 4 200 (optional IG 4 500) installed on the unit behind a privacy door, with electric start 24 volts, with cooling water preheating approx. 5 KW / 400 volts and battery charger including 4-pole generator switch. Prepared for emergency power operation including mains parallel operation, control of a synchronizable external motor-driven power section (mains generator switch), manufactured in accordance with CE guidelines.